Home page > Glazed units 

Since we can combine the PYROBELITE and PYROBEL glass with laminated, coloured, reflexive and low-emission glass, we offer a wide range of glass panes combined with fire-resistant glass. This type of glass may perform different functions, such as: protection against burglary and noise, thermal and light insulation. As we have possibilities to process the fire-resistant glass, all our fire-resistant products are available with very short lead times.

It must be remembered that the process of transforming fire-resistant glass into double-glazed units may not be commissioned to random manufacturers. That process requires specific manufacturing discipline due to the necessity of protecting the glass edges from coming into contact with the gel bonding of the panes by means of special aluminium foil. Direct contact with aggressive substances in the air or in water may lead to the fire-resistant glass layers losing their fire-resistant properties.

Similarly, special precautions must be applied during the fitting of double-glazed sheets in window frames in order to prevent the breaking of the protective layer securing the edges.

The destruction of the protective layer may lead to the glass losing its properties and result in quicker flame propagation, as well as the inability to evacuate people from the building.

In the event of the time spell between the glass manufacture and fitting in the window frame being very long, the inside surface of the fire-resistant glass must be protected from theUV radiation, as it is not protected by means of the PVB foil.

Before orders are processed, clients ought to be notified of the general criteria defined by glass manufacturers, which must be followed during its application. The company which processes the glass sheets into double-glazed units is not responsible for the loss of the fire-resistant properties as a result of inappropriate fitting.

Types of product:

Trade name
Application
Type
Thickness
[mm]

Thickness
tolerance
[mm]

Minimal
dimension *
[mm]
Weight
[kg/
m2]
Rw
(C,Ctr)
[dB]
 LT
[%]
Safety class
EN 12600
U
[W/
m
2K]
PYROBELITE 7 internal

EW30

7,9 +/- 0,9 200 x 400 17 34
(-0,-3)
89 3(B)3 5,7
PYROBELITE 7 EG external

EW30

11,3 +/- 1,0 200 x 400 25 35
(-1,-2)
87 1(B)1 5,5
PYROBEL 8 internal EI15 EW30 9,3 +/- 1,0 200 x 400 20 34
(-1,-3)
88 - 5,6
PYROBEL 8 EG external EI15 EW30 13,1 +/- 1,3 200 x 400 28 36
(-1,-3)
86 1(B)1 5,4
PYROBEL 16 internal EI 30 EW60 17,3 +/- 1,2 300 x 400 40 39
(-1,-3)
84 2(B)2 5,4
PYROBEL 16 EG external EI 30 EW60 21,2 +/- 1,5 300 x 400 48 39
(-1,-3)
83 1(B)1 5,2
PYROBEL 17 internal EI 45 EW60 17,4 +/- 1,5 200 x 400 40 37
(-1,-3)
84 2(B)2 5,4
PYROBEL 17 EG external EI 45 EW60 21,2 +/- 2,0 200 x 400 48 38
(0,-3)
84 1(B)1 5,2
PYROBEL 25 internal EI 60 26,6 +/- 2,0 200 x 400 60 40
(-1,-3)
81 1(B)1 5,2
PYROBEL 25 EG external EI 60 30,4 +/- 2,0 200 x 400 68 43
(-1,-4)
80 1(B)1 5,0
PYROBEL 35 internal EI 90 34,7 +/- 2,0 200 x 400 81 41
(-1,-4)
79 1(B)1 4,9
PYROBEL 35 EG external EI 90 38,5 +/- 2,0 200 x 400 89 42
(-1,-4)
77 1(B)1 4,8
PYROBEL 53 internal EI 120 52,5 +/- 3,0 200 x 400 122 45
(-1,-4)
72 1(B)1 4,5
PYROBEL 53 EG external EI 120 56,2 +/- 3,0 200 x 400 130 46
(-2,-5)
71 1(B)1 4,3
PYROBEL 19 horizontal EI 30 19,1 +/- 1,5 200 x 400 43 38
(-1,-3)
81 1(B)1 5,2
PYROBEL 23 horizontal EI 45 23,7 +/- 1,8 200 x 400 54 39
(0,-3)
80 1(B)1 5,0
PYROBEL 28 horizontal EI 60 28,4 +/- 2,0 200 x 400 63 41
(0,-3)
78 1(B)1 4,9

*Relates to double-glazed glass sheets
**Dimensions tolerance [mm] +/- 2 mm

Selected certificated systems with Pyrobelite i Pyrobel glass:

Trade name System used Maximal dimension *
(height x width.) [mm]
Approval/Certification
Pyrobelite 7 ESCO FERRO-WIC max. area 3,3m2 AT-15-4365/2002
Pyrobelite 7 Jansen Economy 50; 60 max. area 3,3m2, max. height 2,4m AT-15-2777/2004
Pyrobelite 7 Jansen Anisol 2 max. area 3,3m2, max. height 2,3m AT-15-3419/2003
Pyrobelite 7 Jansen Viss fire TV max. area 3,3m2,
max. height 2,4m
NP-797/A/03/ZL
Pyrobel 8 Aluprof MB-78 EI 1200 x 2000 AT-15-6006/2006
Pyrobel 8 Sapa SBF 2074, 3074 1200 x 2000 ITB LP-724/03,
AT-15-4345/2003
Pyrobel 8 Hasil EI 15 1500 x 3000 AT-15-6963/2006
Pyrobel 16 Aluprof MB-78 EI 1400 x 2900** AT-15-6006/2006
Pyrobel 16 Yawal TM 75 EI 1300 x 2400** AT-15-6830/2006
Pyrobel 16 Sapa SBF 2074, 3074 1300 x 2400** AT-15-4345/2003
Pyrobel 16 Sapa SFB 4150 1500 x 2400** NP-1081/A/04/ZL
Pyrobel 16 Schuco FW 50+BF/FW 60+BF 1350 x 2900 AT-15-6630/2005
Pyrobel 16 Schuco Firestop II 1400 x 2656 AT-15-5916/2006
Pyrobel 16 Jansen Janisol 2 1200 x 2300 AT-15-3419/2003
Pyrobel 16 Hasil EI 30 1500 x 3000 AT-15-6963/2006
Pyrobel 16 Mercor Profile ISO 1200 x 2200 AT-15-5025/2003
Pyrobel 16 Jansen Viss Fire 1300 x 1900 NP-797/A/03/ZL
Pyrobel 17 Hardwood 1400 x 2700 Pavus Pr-05-1.02.063
Pyrobel 25 Aluprof MB-78 EI 1400 x 2700** AT-15-6006/2006
Pyrobel 25 Yawal TM 75 EI 1300 x 2400** AT-15-6830/2005
Pyrobel 25 Sapa FSB 2074, 3074 1300 x 2400** AT-15-4345/2003
Pyrobel 25 Schuco FW 50+BF/FW 60+BF 1400 x 2400 AT-15-6630/2005
Pyrobel 25 Schuco Firestop II 1400 x 2455 AT-15-5916/2006
Pyrobel 25 Jansen Janisol 3 1400 x 2300 AT-15-3419/2003
Pyrobel 25 Jansen Viss Fire 1400 x 2700 NP-898/A05/ZL
Pyrobel 25 Alumil Alufire 1200 x 2250 AT-15-6520/2004
Pyrobel 25 Hasil EI 60 1400 x 2000 AT-15-6963/2006
Pyrobel 25 Mercor Profile ISO 1200 x 2200 AT-15-5025/2003
Pyrobel 35 Profil stalowy 1400 x 2700 CTICM 05V274
Pyrobel 53 Mercor Profile ISO max. area 2,0m2,
944 x 2119**
AT-15-6623/2005
Pyrobel 53 Steel profile 1300 x 2600 CTICM 06V074
       
Pyrobel 19 Steel profile 1100 x 2100 Pavus Pr-05-1.02.086
Pyrobel 23 Steel profile 1000 x 2000 Pavus Pr-04-1.02.140
Pyrobel 28 Steel profile 1100 x 2100 Pavus Pr-04-1.02.149
*Maximum dimensions are presented on the basis of test results for complete wall systems. The maximum dimensions can be different for particular wall systems. Maximum dimensions for each system are presented in technical approvals
**also for (height x width) [mm]



 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

What should you know when buying fire resistant glass?

The information provided below contains additional remarks which enable interested parties to find out more details associated with purchasing fire resistant glass units.
 
Due to the requirements with respect to fire resistant glass units, the production and ordering must involve additional procedures which is not the case with other products.
 
The standard market offer of Press-Glas comprises of double glazed fire resistant glass, designed for use in interior or outdoor partition walls. Single glazed fire resistant glass units for outdoor partition walls are available in the non-standard market offer.
 
New cutting and glazed lines for fire resistant glass units enable the production of glass units with dimensions of 2,700 by 5,000 mm. The maximum dimensions used are however limited by technical approvals that define the maximum homologated dimensions of the sides, which normally do not exceed 2,700mm. While ordering glass units it is essential to check the maximum dimensions allowed in the approval each time.

Due to the stability of work with regard to the glass units under the force of fire spacerbars of zinc steel or aluminium are used in the production of double glazed fire resistant glass. The use of the so-called warm edges is limited. Up to now the possibility of using plastic edges has not been considered. The thermal bridge which causes excessive infiltration of heat along the edges of the glass can be immediately reduced by the use of spacerbars of precious steel. Double glazed units are offered as standard and filled with air in a spacerbar of 8mm width, while the full range of spacerbars involves widths between 6 to 24mm. In the case where there is a necessity to achieve the heat transmission coefficient of Ug = 1.1 W/mZK, then glass units are filled with noble gas known as argon, with a spacerbar of 16mm width.

Standard offer of fire resistant glazed units:

Type
*
Product
Width [mm]
Weight [Kg/m2]
EW 30
VSG 44.2 Thermofloat/ 8 / Pyrobelite 7
24
40
EI 15
EW 30
VSG 44.2 Thermofloat/ 8 / Pyrobel 8
25
43
EI 30
EW 60
VSG 44.2 Thermofloat/ 8 / Pyrobel 16
33
63
EI 45
EW 60
VSG 44.2 Thermofloat/ 8 / Pyrobel 17
33
63
EI 60
VSG 44.2 Thermofloat/ 8 / Pyrobel 25
42
83
EI 90
VSG 44.2 Thermofloat/ 8 / Pyrobel 35
52
104
EI 120
VSG 44.2 Thermofloat/ 8 / Pyrobel 53
69
143
 
*The classification of resistance has been presented on the basis of tests carried out for the complete system. In the case of using another system or elements of a different system to that shown in the approvals, the classification of fire-resistance may not be achieved.
 
In the case of ordering double glazed reflexive solar control glass and glass which is edged in mass, it is necessary to receive advice as to the possibility of application due to the limitations associated with the heating of fire resistant glass. This is associated with the phenomenon of heat energy absorption in the glass mass, which in effect can cause degradation of the gel, which is a component of fire resistant glass, under the impact of excessive temperatures.
Construction firms that order double glazed glass often avail of forms which they prepare themselves. However, in the case of ordering fire resistant glass units, orders should be made using forms prepared by Press-Glas. It is necessary to provide the name of the glazing system which will involve the use of glass units and the valid number of the technical approval. Moreover, the form containing the order should include the information provided in the table below:
No.
Glass unit external + position of coating
Type of spacebar + width (mm)
Inside Glass unit
Width (mm)
Height (mm)
Quantity
Glazing system (name and number of technical approval)
               

Press-Glas marks fire resistant glass units known as Pyrobel and Pyrobelite with a permanent stamp which includes the following:
  • marking the type of fire resistant glass: Pyrobel or Pyrobelite,
  • marking of classification as regards resistance,
  • identification symbol of the producer of the glass units: Press-Glas,
  • month and year of production with regard to the glass unit.
Additionally, glass units for inside use are marked with an appropriate label aimed at clearly specifying the designed glazing application.
Assessment of defects in fire resistance glass units is carried out on the basis of the norms known as PN-EN ISO 12543 entitled “Laminated glass and safe laminated glass”.
Realization of standard orders does not exceed 14 days and the period of guarantee commences on the day of final production of the glass units.

» see more about fire-resistant glass


 
 
 
   
 
 
 
  Copyright 2005 Press Glas